Everything else in this section follows vibration because it ends up as
**sound**. This page follows it because it ends up as a **crack**. A pile
driver next door, a tram at the end of the street or a blast on a nearby site
puts vibration into the ground, the ground puts it into a foundation, and the
question the neighbours ask has nothing to do with audibility: will the
building be damaged?

Answering it properly means the dynamic stresses in the structure, compared
against what the material and the design allow. DIN 4150-3 offers the cheap
answer first, and it is the one used in practice: **guideline values**
(*Anhaltswerte*) for a single measured quantity, the peak particle velocity,
drawn from a large body of measurements on real buildings. Keep under them and
damage of the kind the standard defines has not been observed in that body of
measurements, which is a statement about the evidence rather than a promise
about this building: meeting a guideline value satisfies the DIN 4150-3
criterion and certifies nothing. Exceed them and nothing follows automatically. The standard is explicit that damage does not
have to occur; what has run out is the cheap answer, and the stress
calculation has to be done instead.

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/structural_damage_guidelines_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/structural_damage_guidelines.svg" alt="Guideline peak velocity against frequency for the three building classes of DIN 4150-3 Table 1, flat to 10 Hz and rising after it, with the topmost-floor and buried-pipeline values beside it as paired short-term and long-term bars" width="94%"></picture>

<details>
<summary>Show the code for this figure</summary>

```python
import matplotlib.pyplot as plt
import numpy as np
from phonometry import vibration

freq = np.linspace(1.0, 100.0, 400)

fig, ax = plt.subplots()
for name in vibration.BUILDING_CLASSES:
    ax.plot(freq, vibration.guideline_velocity(name, freq), label=name)
ax.set(xlabel="Frequency [Hz]", ylabel="Peak velocity $v_i$ [mm/s]")
ax.grid(True, alpha=0.3)
ax.legend()
plt.show()

# One measurement against the guideline it is judged by, drawn on the same
# curves:
res = vibration.assess_building_vibration(
    4.2, building_class="residential", frequency_hz=18.0
)
print(round(res.guideline_mm_s, 2), res.within_guideline)   # 7.0 True
res.plot()
plt.show()
```

</details>

## 1. What is measured

Clause 5.1 fixes the quantity before it fixes any number. At the
**foundation**, the three components $v_x$, $v_y$ and $v_z$ of the particle
velocity are recorded separately and the largest peak of the three,
$|v_i|_\mathrm{max}$, is the value judged; the standard then writes it $v_i$
and so does this page. The transducers go in the lowest storey, on the
foundation or the outside wall, and on an unbasemented building no more than
0,5 m above ground level, preferably on the side facing the excitation.

In the **topmost floor plane** the quantity changes: the larger of the two
horizontal components, measured in or close to the outside wall. That
measurement is not a second excitation. It is the building's horizontal answer
to the one at its foundation, which is why the guideline value there does not
depend on frequency: the response is already at the structure's own
frequencies.

<picture><source media="(prefers-color-scheme: dark)" srcset="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/diagram_structural_damage_points_dark.svg"><img src="https://raw.githubusercontent.com/jmrplens/phonometry/main/.github/images/diagram_structural_damage_points.svg" alt="Section through a three-storey dwelling with no basement and a piling rig beside it: the foundation point in the lowest storey on the outside wall facing the source, the two horizontal directions in the topmost floor plane, the vertical direction on a floor at mid-span, and a buried pipeline more than 2 metres away, with enlarged details of the foundation point under its 0,5 m limit and of the transducers on the pipe" width="100%"></picture>

**How the measurement goes.** Use a vibration meter that meets DIN 45669-1,
checked and calibrated at a reference frequency and amplitude for the job. At the
foundation, three transducers go close together in the lowest storey, on the
outside wall or its foundation, preferably on the side facing the source and,
without a basement, no higher than 0,5 m above ground level, recording $z$ and
two horizontal directions at right angles, one parallel to a side wall and
preferably $x$ pointing at the source. On a hard surface a transducer set down
loose holds only to 100 Hz vertically and 40 Hz horizontally at 3 m/s² or less.
In the topmost floor plane, $x$ and $y$ go in or close to the outside wall; where
relevant, on the floors expected to vibrate most, $z$ goes at about mid-span; on
a pipeline, the transducers go on the pipe itself, bared only at the measuring
point. Where possible, extraneous vibration is judged by comparing the readings
with and without the source acting. Read the peak of each component and its
frequency, and report what Annex A lists.

## 2. Short-term vibration, and why the guideline rises with frequency

Short-term vibration is vibration that does not occur often enough to build up
resonance in the structure: construction work, blasting, a passing train on a
line that is not busy. Table 1 gives its guideline values for three building
classes, and at the foundation they depend on frequency.

They rise, and the reason is that the standard is really about strain. The
same velocity at a lower frequency means a larger displacement, and it is the
displacement across a wall that opens a crack in the plaster. So a building
tolerates a fast wiggle better than a slow one, and the guideline value climbs
from 1 Hz to 100 Hz. Above 100 Hz the 100 Hz value may be used.

Table 1 prints the middle band as a range, "5 bis 15" for a dwelling between
10 Hz and 50 Hz, and a range does not say what 30 Hz is worth. Bild 1 says it:
the corner values joined by straight lines on a **linear** frequency axis. A
dwelling at 30 Hz is allowed 10 mm/s, and that is a reading of the figure, not
of the table.

```python
from phonometry import vibration

# The corners Table 1 prints, for a dwelling.
for f in (1.0, 10.0, 50.0, 100.0):
    print(f, vibration.guideline_velocity("residential", f))
# 1.0 5.0 / 10.0 5.0 / 50.0 15.0 / 100.0 20.0

# Inside a band, which only Bild 1 decides.
print(vibration.guideline_velocity("residential", 30.0))          # 10.0

# In the topmost floor plane there is nothing to read against frequency,
# and passing one anyway is refused rather than ignored.
print(vibration.guideline_velocity("residential", location="top_floor"))  # 15.0
```

The three classes are the rows of Table 1: `"commercial"` for commercial and
industrial buildings and buildings of like structure, `"residential"` for
dwellings and buildings of like construction or use, and `"sensitive"` for
buildings that fit neither and are worth preserving, a listed building being
the example the standard gives. A massive engineering structure such as a
reinforced-concrete abutment or a block foundation may raise the row 1 values
by up to a factor of two, which is what 5.1 allows provided nothing dangerous
comes of the soil mechanics. The allowance is a sentence of Clause 5 naming
Table 1, so it stops at short-term vibration and the library refuses to carry
it over to Table 3:

```python
print(vibration.guideline_velocity("commercial", 50.0, massive_structure=True))
# 80.0
```

## 3. Floors, and the one number that covers them

A floor or ceiling gets its own sentence rather than a table. Clause 5.2: if
the vertical velocity at the point of largest vibration, in general mid-span,
stays at or below 20 mm/s, no reduction in the serviceability of the floor is
expected. The value is published as `FLOOR_VERTICAL_MM_S`, and for a building
in row 3 of Table 1 the standard notes that even that may have to be reduced.

## 4. Buried pipelines

A pipe in the ground is judged on the pipe, not on the building above it, and
by what it is made of. Table 2 has three rows, and Clause 6.3 lets long-term
vibration use the same table at 50 % without further evidence:

```python
from phonometry import vibration

print(vibration.pipeline_guideline_velocity("welded_steel"))                # 100.0
print(vibration.pipeline_guideline_velocity("masonry_or_plastic"))          #  50.0
print(vibration.pipeline_guideline_velocity(
    "masonry_or_plastic", duration="long_term"))                            #  25.0
```

House connections up to 2 m from the building are judged by the building's own
foundation values instead, and drainage pipes by row 3 whatever they are made
of.

## 5. Long-term vibration

Long-term vibration (*Dauererschütterungen*) is the opposite case: it occurs
often enough for the structure to respond at its own frequencies. Table 3
answers it with one value per class in the topmost floor plane and nothing at
the foundation, because a structure ringing at its own frequency is judged
where it rings. The values run from a quarter to a third of the short-term ones, and the
fraction is not the same for the three classes: 10 against 40, 5 against 15 and
2.5 against 8 mm/s.

```python
from phonometry import vibration

for name in vibration.BUILDING_CLASSES:
    short = vibration.guideline_velocity(name, location="top_floor")
    long = vibration.guideline_velocity(
        name, location="top_floor", duration="long_term"
    )
    print(name, short, long)
# commercial 40.0 10.0 / residential 15.0 5.0 / sensitive 8.0 2.5
```

Asking for a long-term value at the foundation raises, because Table 3 does
not have that column.

## 6. From a velocity to a stress

Clause 6.2 is the bridge back to the proper calculation. For a beam or a
one-way slab of full rectangular section, constant stiffness and uniform mass,
vibrating in one mode, the peak bending stress follows from the peak velocity
alone:

$$
\hat{\sigma}_\mathrm{max} = 1{,}73 \left(E_\mathrm{dyn}\, \varrho\,
\frac{G_\mathrm{ges}}{G_\mathrm{balken}}\right)^{0,5} k_n\, \hat{v}_\mathrm{max}
$$

No length, no depth, no span: the dimensions cancel, which is the whole reason
the formula is worth having. A velocity measured where the amplitude is
largest is enough. The mode coefficient $k_n$ lies between 1 and 1,3 in the
technically important cases, so it can move the answer by less than a third,
and $G_\mathrm{ges}/G_\mathrm{balken}$ is 1 for a beam carrying nothing but
itself.

```python
from phonometry import vibration

# Concrete, 30 GPa dynamic modulus, 2400 kg/m3, first mode, 10 mm/s peak.
# Note the unit: the tables are in mm/s and this formula is in m/s.
sigma = vibration.bending_stress(
    0.010, dynamic_modulus_pa=3.0e10, density_kg_m3=2400.0
)
print(round(sigma / 1e6, 2), "MPa")     # 0.15 MPa
```

Clause 6.4 adds the estimate that says whether the topmost floor plane will
answer at all: for a building of about five storeys or more, the lowest
horizontal natural frequency is roughly $f_i \approx 10/n$ with $n$ the number
of storeys.

```python
print(vibration.storey_fundamental_frequency(10))    # 1.0 Hz
```

Below that, `BuildingDamageWarning` says so: four storeys still return
2.5 Hz, because "about five" is not a line the standard drew, but the number
is an extrapolation of a rule offered for taller buildings rather than the
rule itself.

## See also

- [Evaluating machine vibration (ISO 20816-1)](https://jmrplens.github.io/phonometry/vibration/machinery/machine-vibration-evaluation/):
  the same shape of question asked of a machine rather than of a building.
- [Human vibration exposure (ISO 2631, ISO 5349)](https://jmrplens.github.io/phonometry/vibration/human/human-vibration/):
  what the same vibration does to a person.
- [Transfer stiffness of resilient elements (ISO 10846)](https://jmrplens.github.io/phonometry/vibration/structural/transfer-stiffness/):
  the elements inserted to keep the vibration out in the first place.

## References

- Deutsches Institut für Normung. (1999). *Erschütterungen im Bauwesen — Teil
  3: Einwirkungen auf bauliche Anlagen* (DIN 4150-3:1999-02).
  The measured quantity of 5.1, the short-term guideline values of Table 1
  with the curves of Bild 1, the ceiling rule of 5.2, the buried-pipeline
  values of Table 2, the long-term values of Table 3 and the 50 % reduction of
  6.3, the bending stress of Formula (1) in 6.2 and the storey estimate of
  6.4. The measuring points, directions and report of 5.4, the pipeline notes
  of D.1 and the worked dwelling of D.2 are prose, set out in the measurement
  section.
- Deutsches Institut für Normung. (2005). *Messung von Schwingungsimmissionen —
  Teil 2: Messverfahren* (DIN 45669-2:2005-06). Where the transducers of a
  building measurement go and how they are set down: the foundation positions
  of 5.1.2, the measuring directions of 5.2, the loose-mounting limits of
  5.3.2, the measurement time of 6.1, the check before use of 6.3 and the
  comparison with the source stopped of 7.2.2.

## Standards

DIN 4150-3:1999-02, *Erschütterungen im Bauwesen — Teil 3: Einwirkungen auf
bauliche Anlagen*: the guideline values for the peak particle velocity by
building class, measurement location and how often the vibration occurs
(Tables 1, 2 and 3, with Bild 1 fixing the reading between the printed corner
values), the vertical value for floors (5.2), the doubling of row 1 for
massive engineering structures (5.1), the 50 % reduction of the pipeline table
for long-term vibration (6.3), the bending stress of Formula (1) in 6.2 and
the storey estimate of 6.4. Prediction (DIN 4150-1), human perception in
buildings (DIN 4150-2) and the instrument requirements of DIN 45669 are not
implemented.